67606INTER-REGIONAL TRANSFER06/03/2019 02:09:51 PM

Planned outage of Heywood 500 kV Bus at Heywood in the VIC region, on 07/03/2019

AEMO ELECTRICITY MARKET NOTICE

The Heywood No. 2 500 kV Bus, Heywood M2 transformer and Heywood 500 kV CB (213) at Heywood in the Victoria region are planned to be out of service from 1700 hrs on 07/03/2019 to 1900 hrs on 07/03/2019.

A credible contingency event during this planned outage could cause synchronous separation of the South Australia (SA) region from the rest of the NEM. If separation occurs, load may be interrupted due to the operation of the Automatic Under Frequency Load Shedding (AUFLS) scheme in SA.

The credible separation contingency is managed as follows:
When power transfer is from SA to Victoria, contingency lower FCAS will be sourced from SA.
When power transfer is from Victoria to SA, due to the 47-52Hz Island separation frequency band advised by the SA jurisdiction, contingency raise FCAS is not sourced in SA and the AUFLS scheme may respond to low frequency events.

Forecast capacity reserves in the SA region are currently sufficient to meet electricity demand during the planned outage.

The following constraint sets have been invoked for this outage:
F-I-HYSE
I-VS_050
S-X_BC_CP
V-HYTX_M12
V-HY_500BUS

Refer AEMO Network Outage Schedule (NOS) for further details.

Harmohan Singh
Operations
67605RECLASSIFY CONTINGENCY06/03/2019 12:20:53 PM

Reclassification of a Non-Credible Contingency Event: Clare South- King Creek 7128/2 132kV line and Strathmore - Clare South 7208 132kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits to now be more likely and reasonably possible. Accordingly AEMO has reclassified it as a credible contingency event.

Region: QLD1

Lines: Clare South- King Creek 7128/2 132kV and Strathmore - Clare South 7208 132kV

Duration: 06/03/2019 12:20 until further notice

Constraint set(s) invoked:
NONE

Auto-generated on behalf of Manager NEM Real Time Operations
67604RECLASSIFY CONTINGENCY06/03/2019 12:08:35 PM

Reclassification of a Non-Credible Contingency Event: Collinsville - Stoney Creek No.7306 132 kV line and Collinsville - Newlands No.7121 132 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits to now be more likely and reasonably possible. Accordingly AEMO has reclassified it as a credible contingency event.

Region: QLD1

Lines: Collinsville - Stoney Creek No.7306 132 kV and Collinsville - Newlands No.7121 132 kV

Duration: 06/03/2019 12:08 until further notice

Constraint set(s) invoked:
NONE

Auto-generated on behalf of Manager NEM Real Time Operations
67603RECLASSIFY CONTINGENCY06/03/2019 11:54:00 AM

Reclassification of a Non-Credible Contingency Event: Ross - Chalumbin No.857 275 kV line and Ross - Chalumbin No.858 275 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits to now be more likely and reasonably possible. Accordingly AEMO has reclassified it as a credible contingency event.

Region: QLD1

Lines: Ross - Chalumbin No.857 275 kV and Ross - Chalumbin No.858 275 kV

Duration: 06/03/2019 11:53 until further notice

Constraint set(s) invoked:
NONE

Auto-generated on behalf of Manager NEM Real Time Operations
67602RECLASSIFY CONTINGENCY06/03/2019 11:22:35 AM

Reclassification of a Non-Credible Contingency Event: Hazelwood - Rowville No.1 220kV line and Hazelwood - Rowville No.2 220kV line in VIC1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits to now be more likely and reasonably possible. Accordingly AEMO has reclassified it as a credible contingency event.

Region: VIC1

Lines: Hazelwood - Rowville No.1 220kV and Hazelwood - Rowville No.2 220kV

Duration: 06/03/2019 11:22 until further notice

Constraint set(s) invoked:
V-HWRO_R_N-2 Constraint set contains the following interconnector(s) on the left hand side:
NONE


Auto-generated on behalf of Manager NEM Real Time Operations
67601RECLASSIFY CONTINGENCY06/03/2019 11:14:45 AM

Cancellation of a Non-Credible Contingency Event: Goonyella - Nth Goonyella T- Stoney Creek 7122 132 kV line and Goonyella - Newlands No. 7155 132 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits is no longer reasonably possible. There is no longer any lightning activity in the vicinity of the following lines. Accordingly its classification has reverted to a non-credible contingency event.

Region: QLD1

Lines: Goonyella - Nth Goonyella T- Stoney Creek 7122 132 kV and Goonyella - Newlands No. 7155 132 kV

Cancellation time: 06/03/2019 11:14

Constraint set(s) revoked:
NONE

Refer AEMO Electricity Market Notice 67592

Auto-generated on behalf of Manager NEM Real Time Operations
67600RECLASSIFY CONTINGENCY06/03/2019 11:09:48 AM

Cancellation of a Non-Credible Contingency Event: Moranbah - Goonyella No.7370 132 kV line and Moranbah - Goonyella No.7369 132 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits is no longer reasonably possible. There is no longer any lightning activity in the vicinity of the following lines. Accordingly its classification has reverted to a non-credible contingency event.

Region: QLD1

Lines: Moranbah - Goonyella No.7370 132 kV and Moranbah - Goonyella No.7369 132 kV

Cancellation time: 06/03/2019 11:09

Constraint set(s) revoked:
NONE

Refer AEMO Electricity Market Notice 67599

Auto-generated on behalf of Manager NEM Real Time Operations
67599RECLASSIFY CONTINGENCY06/03/2019 10:04:41 AM

Reclassification of a Non-Credible Contingency Event: Moranbah - Goonyella No.7370 132 kV line and Moranbah - Goonyella No.7369 132 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits to now be more likely and reasonably possible. Accordingly AEMO has reclassified it as a credible contingency event.

Region: QLD1

Lines: Moranbah - Goonyella No.7370 132 kV and Moranbah - Goonyella No.7369 132 kV

Duration: 06/03/2019 10:04 until further notice

Constraint set(s) invoked:
NONE

Auto-generated on behalf of Manager NEM Real Time Operations
67598RECLASSIFY CONTINGENCY06/03/2019 09:54:45 AM

Cancellation of a Non-Credible Contingency Event: Moranbah - Goonyella No.7370 132 kV line and Moranbah - Goonyella No.7369 132 kV line in QLD1 due to Lightning.

AEMO ELECTRICITY MARKET NOTICE

Cancellation of reclassification of a Non-Credible Contingency Event as a Credible Contingency Event due to Lightning. AEMO considers the simultaneous trip of the following circuits is no longer reasonably possible. There is no longer any lightning activity in the vicinity of the following lines. Accordingly its classification has reverted to a non-credible contingency event.

Region: QLD1

Lines: Moranbah - Goonyella No.7370 132 kV and Moranbah - Goonyella No.7369 132 kV

Cancellation time: 06/03/2019 09:54

Constraint set(s) revoked:
NONE

Refer AEMO Electricity Market Notice 67594

Auto-generated on behalf of Manager NEM Real Time Operations