Market Notices

87974NON-CONFORMANCE10/07/2021 04:50:16 AM

NON-CONFORMANCE Region SA1 Saturday, 10 July 2021

AEMO ELECTRICITY MARKET NOTICE

NON-CONFORMANCE SA1 Region Saturday, 10 July 2021

AEMO declared a schedule generating unit non-conforming

Unit: OSB-AG
Duration: 10/07/2021 04:40 to 10/07/2021 04:50
Amount: 12 MW
Constraint: NC-S_OSB-AG

Auto-generated on behalf of Manager NEM Real Time Operations
87973GENERAL NOTICE09/07/2021 05:14:01 PM

Planned outage of Heywood 500kV bus no 2 outage in Victoria (VIC) region on 14, 21,22,23 July 2021

AEMO ELECTRICITY MARKET NOTICE

This market notice is FOR INFORMATION ONLY.

Heywood 500kV bus no 2 outages is planned to be out on the following periods.

-0700 hrs to 1700 hrs on 14 July 2021
-0700 hrs to 1700 hrs on 21 July 2021
-0700 hrs to 1700 hrs on 22 July 2021
-0700 hrs to 1700 hrs on 23 July 2021

A credible contingency event during this planned outage could cause synchronous separation of the South Australia (SA) region from the rest of the NEM. If separation occurs, load may be interrupted due to the operation of the Automatic Under Frequency Load Shedding (AUFLS) scheme in SA.

The credible separation contingency is managed as follows:

When power transfer is from SA to Victoria (Vic), contingency lower FCAS will be sourced from SA.
When power transfer is from Vic to SA, due to the 47-52Hz island separation frequency band advised by the SA jurisdiction, contingency raise FCAS is not sourced in SA and the AUFLS scheme may respond to low frequency events.
Power transfer will be restricted on Victoria - South Australia interconnector (Heywood interconnector).

Forecast capacity reserves in the SA region are currently sufficient to meet electricity demand during the planned outage.

The following constraint sets have been invoked for this outage:

F-I-HYSE
I-VS_050
S-X_BC_CP
V-HYTX_M12
V-HY_500BUS

Refer AEMO Network Outage Schedule (NOS) for further details.


AEMO Operations
87972GENERAL NOTICE09/07/2021 11:29:37 AM

Outage Cancelled: Planned outage of Heywood-Mortlake PS 500 kV line in Victoria region on 14 July 2021

AEMO ELECTRICITY MARKET NOTICE

Refer to AEMO Electricity Market Notices 87715.

The Heywood-Mortlake PS 500 kV line in the Victoria (VIC) region was planned to be out of service on 14/07/2021. This outage is now cancelled.

All constraint sets associated with this outage have been revoked.

AEMO Operations
87971GENERAL NOTICE09/07/2021 11:34:16 AM

Cancellation of Basslink outage on 14 July 2021

AEMO ELECTRICITY MARKET NOTICE

This has reference to the Market Notice 87956 issued on 8 July 2021.

Basslink Pty Ltd have cancelled the previously planned outage for modifications to its control systems on 14 July 2021.

Manager Congestion and Grid Modelling
AEMO Operations
87970INTER-REGIONAL TRANSFER09/07/2021 09:35:32 AM

Inter-regional transfer limit variation - Yass to Wagga132 990 132kV line - NSW region - 09/07/2021

AEMO ELECTRICITY MARKET NOTICE

Inter-regional transfer limit variation - Yass to Wagga132 990 132kV line - NSW region - 09/07/2021

At 0912 hrs 09/07/2021 there was a short notice outage of the Yass to Wagga132 990 132kV line.

The following constraint set invoked at 0920 hrs 09/07/2021
N-X_WGYS_990_991

This constraint set contains equations with the following interconnectors on the LHS.
V-S-MNSP1
VIC1- NSW1

Refer to the AEMO Network Outage Scheduler for further information.

Manager NEM Real Time Operations
87969GENERAL NOTICE09/07/2021 08:07:10 AM

Planned outage of Heywood to Mortlake power station No. 2 line No. 2 bus 500kV Circuit Breaker (213) in the Victoria (VIC) region from 0500 hrs to 0700 hrs on 12th July 2021

AEMO ELECTRICITY MARKET NOTICE

This market notice is FOR INFORMATION ONLY.

A credible contingency event during this planned outage could cause synchronous separation of the South Australia (SA) region from the rest of the NEM. If separation occurs, load may be interrupted due to the operation of the Automatic Under Frequency Load Shedding (AUFLS) scheme in SA.

The credible separation contingency is managed as follows:

When power transfer is from SA to Victoria (Vic), contingency lower FCAS will be sourced from SA.
When power transfer is from Vic to SA, due to the 47-52Hz island separation frequency band advised by the SA jurisdiction, contingency raise FCAS is not sourced in SA and the AUFLS scheme may respond to low frequency events.
Power transfer will be restricted on Victoria - South Australia interconnector (Heywood interconnector).

Forecast capacity reserves in the SA region are currently sufficient to meet electricity demand during the planned outage.

The following constraint sets have been invoked for this outage:

F-I-HYSE
I-VS_050
S-X_BC_CP
V-HYCB_210_213

Refer AEMO Network Outage Schedule (NOS) for further details.


AEMO Operations
87968NON-CONFORMANCE09/07/2021 06:40:14 AM

NON-CONFORMANCE Region NSW1 Friday, 9 July 2021

AEMO ELECTRICITY MARKET NOTICE

NON-CONFORMANCE NSW1 Region Friday, 9 July 2021

AEMO declared a schedule generating unit non-conforming

Unit: MP1
Duration: 09/07/2021 06:30 to 09/07/2021 06:40
Amount: -46 MW
Constraint: NC-N_MP1

Auto-generated on behalf of Manager NEM Real Time Operations
87967NON-CONFORMANCE08/07/2021 08:05:14 PM

NON-CONFORMANCE Region NSW1 Thursday, 8 July 2021

AEMO ELECTRICITY MARKET NOTICE

NON-CONFORMANCE NSW1 Region Thursday, 8 July 2021

AEMO declared a schedule generating unit non-conforming

Unit: VP6
Duration: 08/07/2021 20:00 to 08/07/2021 20:05
Amount: -23 MW
Constraint: NC-N_VP6

Auto-generated on behalf of Manager NEM Real Time Operations
87966MARKET SYSTEMS08/07/2021 03:37:56 PM

CHG0065250 : Planned Outage - MSATS Pre-production Data refresh (CATS and EMDM)

Change Number:CHG0065250
Notification:Market Notice
Type:Initial
Change Type:Normal
Service/ Component: MSATS-Consumer Administration and Transfer Solution(CATS)
Title: Planned Outage-MSATS Pre-Prod Data refresh (CATS & EMDM)

Change Start Date & Time: 12/07/2021 08:00:00 AEST
Change End Date & Time: 21/07/2021 18:00:00 AEST
Outage Start Date & Time: 12/07/2021 08:00:00 AEST
Outage End Date & Time: 18/07/2021 18:00:00 AEST

Description:
Planned Outage - MSATS Pre-Prod Data refresh (CATS and EMDM)
Environment:Pre-Prod
Impact & Requirements:
This change is to advise participants that MSATS Pre-Prod data for CATS and eMDM databases will be refreshed from Prod data. The aim of this data refresh is to update Pre-Prod with Prod data in preparation for the 5 min settlement Market Trials commencing 19/07/2021.

Implications:
The data refresh will be from MSATS Prod data as of approximately Mon 12/072021.
Participants should be aware of:
o Pre-Prod will be unavailable for the duration of the refresh (See above times)
o AEMO will be testing a new refresh process that could potentially shorten the Refresh outage period, participants will be notified of the outage completion which may be earlier than the notified outage.
o Any test NMI data configurations within the Pre-Prod environment will be over written
o Pre-Prod participant passwords will be retained.

The following actions will also be undertaken:
o Pending reports from prod will be stopped and will not execute in Pre-Prod.
o Change requests will continue to process in Pre-Prod after the copy. Notifications as a result of these change requests being processed will be delivered in Pre-Prod.
o Undelivered notifications in Prod at the time of the copy will not be delivered in Pre-Prod.
o Participant outbox/inbox contents will not be copied to Pre-Prod.
o XML output pending delivery to participant outboxes in Prod will be purged from the copy and not delivered in Pre-Prod.
X
Cookies help us improve your website experience.
By using our website, you agree to our use of cookies.
Confirm