Inter-regional transfer limit variation: Hazelwood - South Morang No 1 500 kV Line (VIC) - Voltage Control
The Hazelwood - South Morang No 1 500 kV Line has been de-energised to manage voltages in the Victoria region.
The following constraint set was invoked at 0100 hrs 07/09/2021.
V-HWSM
The constraint set contains equations with the following interconnectors on the LHS.
T-V-MNSP
V-S-MNSP1
V-SA
VIC1-NSW1
Refer to AEMO Network Outage Scheduler (NOS) for return to service details
Manager NEM Real Time Operations
Update - Planned outage of Heywood No.1 500 kV busbar and Heywood - Tarrone 500 kV line in the Victoria region on 07, 08 and 10 September 2021
Refer to MN 90171.
The Heywood No.1 500 kV busbar and Heywood - Tarrone 500 kV line in the Victoria (VIC) region are now planned to be out of service from:
0900 hrs to 2000 hrs on 07/09/2021;
0900 hrs to 2000 hrs on 08/09/2021; and
1600 hrs to 1800 hrs on 10/09/2021.
A credible contingency event during this planned outage could cause synchronous separation of the South Australia (SA) region from the rest of the NEM. If separation occurs, load may be interrupted due to the operation of the Automatic Under Frequency Load Shedding (AUFLS) scheme in SA.
The credible separation contingency is managed as follows:
- When power transfer is from SA to VIC, contingency lower FCAS will be sourced from SA.
- When power transfer is from VIC to SA, due to the 47-52Hz island separation frequency band advised by the SA jurisdiction, contingency raise FCAS is not sourced in SA and the AUFLS scheme may respond to low frequency events.
- Power transfer will be restricted on VIC - SA interconnector (Heywood interconnector) to manage system security following the loss of the next contingency.
Forecast capacity reserves in the SA region are currently sufficient to meet electricity demand during the planned outage.
The following constraint sets have been invoked for this outage:
V-HYTR
F-I-HYSE
S-X_BC_CP
V-HYTX_M12
V-HY_500BUS
I-VS_050
Refer AEMO Network Outage Schedule (NOS) for further details.
AEMO Operations
CHG0069771:MSATS - Consumer Administration and Transfer Solution(CATS)
Change Number: CHG0069771
Notification issued to: Market Notice
Notification Type: Initial
Change Type: Normal
Service/ Component: MSATS - Consumer Administration and Transfer Solution(CATS)
Change Title: 5MS - Market Trials Defect Release (Pre-Prod)
Change Start Date & Time: 07/09/2021 18:00:00 AEST
Change End Date & Time: 08/09/2021 16:00:00 AEST
Outage Start Date & Time: 07/09/2021 18:00:00 AEST
Outage End Date & Time: 07/09/2021 20:00:00 AEST
Change Description:
This outage is to allow the deployment of MSATS and eEMDM Pre-Production as part of 5MS Market Trials . MSATS will be unavailable during this outage period.
Environment: Pre-Production
Participant Impact and Requirements:
There will be no access to the Pre-Production MSATS system for the duration of the outage. Please access outside these hours.
Support Information:
Report any impacts to the AEMO Information and Support Hub or on External 1300 236 600.
Cancellation - AEMO Intervention Event - Intervention dispatch intervals - Direction SA region - 06/09/2021
Cancellation - AEMO Intervention Event - Intervention dispatch intervals - Direction SA region - 06/09/2021
Refer Market Notice 90253
The AEMO Intervention Event and all associated directions are cancelled from 1400 hrs 06/09/2021
Manager NEM Real Time Operations
Direction - SA Region - 06/09/2021
Direction - SA Region - 06/09/2021
In accordance with section 116 of the National Electricity Law, AEMO has issued a direction to a participant in the SA region. For the purposes of the National Electricity Rules this is a direction under clause 4.8.9(a).
The direction was necessary to maintain the power system in a secure operating state.
AEMO may issue or revoke additional directions in order to meet the current requirement, unless sufficient market response is provided. A further market notice will be issued when all directions related to this requirement have been cancelled.
The issue of the direction commences an AEMO intervention event. AEMO declares all dispatch intervals during the event to be intervention dispatch intervals, commencing from the interval ending 0535 hrs on 06/09/2021.
Intervention pricing does not apply to this AEMO intervention event.
Manager NEM Real Time Operations
Update - Possible intervention to manage power system security in South Australia (SA) Region
Update - Possible intervention to manage power system security in South Australia (SA) Region
Refer AEMO Electricity Market Notice 90246
The synchronous generating units currently expected to be synchronised in SA from 0800 hrs 06/09/2021 to 1400 hrs 06/09/2021 will be inadequate to maintain sufficient system strength in SA and hence a secure operating state.
AEMO estimates that, in the absence of sufficient market response by 0530 hrs 06/09/2021, AEMO may need to intervene by issuing a direction requiring one or more SA synchronous generating unit(s) to operate or remain synchronised to maintain power system security in SA.
Manager NEM Real Time Operation
Cancellation - AEMO Intervention Event - Intervention dispatch intervals - Direction SA region - 04/09/2021
Cancellation - AEMO Intervention Event - Intervention dispatch intervals - Direction SA region - 04/09/2021
Refer Market Notice 90217
The AEMO Intervention Event and all associated directions are cancelled from 1800 hrs 05/09/2021
Manager NEM Real Time Operations
Possible intervention to manage power system security in South Australia (SA) Region
Possible intervention to manage power system security in South Australia (SA) Region
The synchronous generating units currently expected to be synchronised in SA from 0900 hrs 06/09/2021 will be inadequate to maintain sufficient system strength in SA and hence a secure operating state.
AEMO may need to intervene by issuing a direction requiring one or more SA synchronous generating unit(s) to operate or remain synchronised to maintain power system security in SA.
Manager NEM Real Time Operation
Inter-regional transfer limit variation - NSWregion - 05/09/2021
Inter-regional transfer limit variation - NSWregion - 05/09/2021
At 0912 hrs 05/09/2021 there was an unplanned outage of the Bannaby - Sydney West (39) 330kV line.
The following constraint set(s) invoked at 0920 hrs 05/09/2021
N-BYSW_39_15M
This constraint set(s) contains equations with the following interconnectors on the LHS.
N-Q-MNSP1
NSW1 - QLD1
VIC1- NSW1
Refer to the AEMO Network Outage Scheduler for further information.